Low voltage cabinet GCS
成功應(yīng)用案例 +
Product description
GCS low-voltage out type switch equipment in line with the requirements of GB7251.1\JB/T9661\IEC439-1 standard applicable to rated voltage 380~660V, 50 ~ 60Hz three-phase AC power system, as distribution, motor control and reactive power compensation, according to different needs can be designed into a mixed system of drawer type and fixed type pumping, the indoor use.
technical parameter
Main circuit rated voltage V | Exchange 380, 660 | |
Auxiliary circuit rated voltage V | AC 220, 380 DC 110, 220 | |
Rated frequency HZ | 50(60) | |
Rated insulation voltage V | 660(1000) | |
Rated current A | ≤4000 | |
Rated current of vertical busbar A | 1000 | |
Bus rated short-time withstand current KA/Is | 50、80 | |
Bus rated peak withstand current KA/Is | 105、176 | |
Power frequency withstand voltage V/min | Main circuit | 2500 |
Auxiliary circuit | 2000 | |
a bus or bus bar | Three-phase four wire system | A、B、C、PEN |
Three-phase five wire system | A、B、C、N、PE | |
The main circuit connector A | 250、400 | |
The control circuit of A connector | 10、20 | |
Protection level | IP30、IP40 |